about-banner-image


Star Delta Motor Starter Type LK1

The LK1 Star Delta motor starters are available in 2 identical distinct designs, suitable wired & inter-connected with three solenoid operated air break contactors Type LK1 and one triple pole thermal overload relay Type LK1, fopr overload & under voltage protection It is available in Semi Automatic & Fully Automatic version in 16A & 25A contactor ratings. In the Semi-automatic version, the motor starts in STAR on pressing the START button & changes over to DELTA on releasing the start button after the motor has picked up its full speed. In the Fully-Automatic version, the changeover from STAR to DELTA is controlled by an adjustable electronic timer & the user needs to press the Start button only once, where from the timer take over.

Scan QR Code to Download Brochure

QR Code

Ratings / Specifications:

  • Contactor Type LK1 ( 16A/25A)  + Relay Type LK1
  • Suitable for 3 Phase motors upto 15 HP
  • Relay ranges: 6-10A, 9-14A, 13-21A, 20-32A
  • Coil Voltage: 360V / 440V / 415V Wide band
  • Nominal rating: 15A 500V AC / 25A 500V AC
  • Spares Available : Air Break Contactor, Thermal Overload Relay Unit, No Volt Coil, Spare Power Contact Kits, Push Button, Auxilliary Contact Block , Star Delta Timer


Application:

  • Agriculture & Industry application


Dimension Details:

  • Weight: 4.76 kgs (SASD-16A in sheet steel enclosure)
  • Dimensions: 221(H)X399(W)X115(D)mm